DC3000 Formula

kbrattonInformationLeave a Comment

Formula

Do you know how many dc3000 air cleaners you will need to clean your work space?
See the formula sheet for table and see steps below!

FORMULA TO DETERMINE NUMBER OF UNITS NEEDED:
STEP 1: Determine the (Air Exchange Rate) from the Table below that best fits your application needs.
STEP 2: Determine the total cubic feet of your plant work area –
Total cubic feet = L x W x H (maximum height 20’)
Where:
L = length of your work space (feet)
W = width of your work space (feet)
H = height of your ceiling in the work space (feet)
STEP 3: Divide the total cubic feet by the AER determined in Step 1.
STEP 4: Divide this total by the CFM of the unit you prefer to use.
dc3000 is 3000 CFM
STEP 5: Determine the best location or placement for units.
*Source capture may be required to meet OSHA, PEL or TWA requirements. General guidelines only.